logo

Compact reciprocating heat pumps for high efficiency heating

The GEA RedGenium is a compact, energy-efficient heat pump designed for small- to medium-capacity industrial heating. Based on the successful GEA BluGenium chiller concept, this series is highly adaptable, low in ammonia charge, and arrives fully piped, wired, and ready for installation.

At the core of the range is the GEA Grasso V XHP series, delivering supply temperatures up to 95 °C – the only standard reciprocating heat pump on the market to achieve this level. For mid-range requirements, the GEA Grasso V HP (up to 70 °C) and Grasso 5HP (up to 80 °C) models offer cost-effective, high-efficiency solutions.

The RedGenium is ideal for process heat in industrial operations and integration into district heating networks. It can draw heat from diverse sources – Including wastewater and groundwater – or utilize an optional cascade evaporator to recover waste heat directly from existing refrigeration systems.

Talk to an expert
arrow

Key features and highlights

  • Heating capacity: Approx. 200 – 3,000 kW
  • High-temp supply: Up to 95 °C
  • Heat sources: -10 °C to 50 °C (60 °C with V XHP)
  • Sustainability: Up to 25% energy savings and equivalent CO2 reduction
  • Natural refrigerant: Ammonia (R717); fully F-gas compliant
  • Versatility: Combined cooling/heating and seamless refrigeration integration
  • Design: Compact, single-piece, and ready-to-connect
  • Precision control: Stepless capacity via frequency inverter (500–1,500 rpm)
  • Smart monitoring: GEA Omni control panel for advanced optimization
Key features and highlights

Technical data

TypeHeat carrier (°C) inlet/outletSec. refrigerant (°C)Heating capacity (kW)¹Cooling capacity (kW)COP²
Stand-alone version (evaporator charged with liquid refrigerant)
GEA RedGenium 3550/7027/221901554.84
GEA RedGenium 3570/8032/272051604.19
GEA RedGenium 4550/7027/222552104.92
GEA RedGenium 4570/8032/272752154.27
GEA RedGenium 5550/7027/223202654.94
GEA RedGenium 5570/8032/273452704.26
GEA RedGenium 6550/7027/223803104.97
GEA RedGenium 6570/8032/274103204.30
GEA RedGenium 30050/7027/225554555.13
GEA RedGenium 45050/7027/228356855.12
GEA RedGenium 60050/7027/2211209205.15
GEA RedGenium 35050/7027/227306005.06
GEA RedGenium 35070/9037/329057154.33
GEA RedGenium 35070/9542/3711959755.05
GEA RedGenium 55050/7027/2210908955.09
GEA RedGenium 55070/9037/32135010654.33
GEA RedGenium 55070/9547/42177514505.07
GEA RedGenium 75050/7027/22144011755.04
GEA RedGenium 75070/9037/32179514154.34
GEA RedGenium 75070/9547/42238519505.10
GEA RedGenium 95050/7027/22180014755.08
GEA RedGenium 95070/9037/32220017264.27
GEA RedGenium 95070/9547/42299524605.17

Technical data

TypeHeat carrier (°C) inlet/outletHeat source condensing (°C)Heating capacity (kW)¹Cooling capacity (kW)COP²
Add-on version (cascade evaporator charged with ammonia from low-pressure chiller)
GEA RedGenium 3550/7030.02351955.67
GEA RedGenium 3570/8030.02151704.36
GEA RedGenium 4550/7030.03162655.78
GEA RedGenium 4570/8030.02902334.45
GEA RedGenium 5550/7030.03953305.81
GEA RedGenium 5570/8030.03552804.37
GEA RedGenium 6550/7030.04653905.70
GEA RedGenium 6550/7030.04303404.42
GEA RedGenium 30050/7030.06655655.90
GEA RedGenium 45050/7030.010008455.96
GEA RedGenium 60050/7030.0133011255.93
GEA RedGenium 35050/7030.08757355.84
GEA RedGenium 35070/9030.08056203.99
GEA RedGenium 35070/9548.0200016755.56
GEA RedGenium 55050/703.0130011005.87
GEA RedGenium 55070/903.012009254.01
GEA RedGenium 55070/9548.0263521955.56
GEA RedGenium 75050/703.0174014705.89
GEA RedGenium 75070/903.0158512254.00
GEA RedGenium 75070/9548.0263521955.56
GEA RedGenium 95050/703.0217018356.02
GEA RedGenium 95070/903.0198015204.00
GEA RedGenium 95070/9548.0323026855.50

¹ at 1500 min⁻¹, ² COP (coefficient of performance) = heating capacity / electrical consumption at net